Baumüller BM1425 – b maXX 1000 Frequency Converter, 2.2kW
Price: Contact
Brand: Baumuller Vietnam
Category: Inverter - Biến tần
Supplier: AnhNghiSon
Origin: Germany
Baumüller BM1425-01-00-01 is an industrial AC frequency converter belonging to the b maXX 1000 product family.
Manufacturer-Verified BM1425 Specifications:
-
Manufacturer: Baumüller
-
Product Family: b maXX 1000
-
Model: BM1425-01-00-01
-
Product Type: Frequency Converter / AC Inverter
-
Frame Size: 2
-
Typical Motor Power: 2.2 kW
-
Rated Output Current: 5.5 A
-
Maximum Output Current: 8.25 A
-
Overload Factor: 1.5
-
Overload Duration: 60 seconds
-
Input Supply: Three-phase 380–480 VAC ±10%
-
Supply Frequency: 47–63 Hz
-
Switching Frequency: 1–15 kHz
-
Adjustable Output Frequency: 0.1–400 Hz
-
Protection Rating: IP20
-
Dimensions, W × H × D: 100 × 174 × 152 mm
The published height and depth include mounting brackets. The depth does not include the required cable bending clearance.
Product-Family Features:
-
Vector control for standard AC motors.
-
Integrated standard EMC filter.
-
Drive monitoring and protection functions.
-
15 preset speeds.
-
CANopen connectivity as described in the product-family documentation.
-
Published operating temperature range: -10°C to +50°C, subject to installation conditions; the upper limit may be reduced to +40°C when units are mounted closely together.
Product Identification:
-
Requested Model: BM1425-01-00-01
-
Distributor-Reported Article Number: 00399882
-
Supply Category: Three-phase 400V frequency converter.
Details Requiring Verification:
-
Manufacturer article number on the actual product nameplate.
-
Current production and stock availability.
-
Hardware and firmware revisions.
-
Communication configuration and included accessories.
-
Compatibility with an existing drive installation.
-
Applicable derating requirements.
Important: The 2.2kW value is the manufacturer's typical motor rating. Final drive selection must consider the motor's rated current, load characteristics and operating conditions.
Safety Notice: Hazardous voltage may remain in the DC-link capacitors after disconnection from the mains supply. Installation and maintenance must be performed by qualified personnel following the manufacturer's safety instructions.