1. Product Identification

Manufacturer: HAUBER-Elektronik.

Model: HE055.2.1.1.001.

Series: HE055.

Product Family: HE05x Smart Condition Monitoring.

Product Type: Smart Vibration Sensor.

Communication Interface: IO-Link.

2. Measurement Specifications

Vibration Velocity RMS: 0–256 mm/s.

Vibration Acceleration RMS: 0–34 g.

Acceleration Peak Hold: 0–48 g.

Dynamic Raw Acceleration: −48 to +48 g.

Bearing Condition Indicator: 0–3.

Crest Factor: 0–100.

Temperature Measuring Range: −50 to +100°C.

3. Frequency Range and Signal Processing

Configurable Velocity and Acceleration RMS Frequency Range: 1–50 Hz to 1–1,000 Hz.

Dynamic Raw Acceleration Frequency Range: Up to 12,000 Hz.

Crest Factor Frequency Range: 10–10,000 Hz.

Maximum Dynamic Data Sampling Rate: 64 kHz.

RMS Averaging Time: 11 seconds.

Reference RMS Response: 99% after 55 seconds.

Peak Hold Time: 4 seconds.

Adjustable Delay Time: 0–60 seconds.

4. Measurement Accuracy

Velocity Reading Resolution: 0.01 mm/s.

Acceleration Reading Resolution: 0.01 g.

Temperature Reading Resolution: 1°C.

Reference Accuracy: ±10% according to DIN ISO 2954.

Calibration Point Accuracy: ±0.5%.

Calibration Point: 1 g RMS at 159.2 Hz.

Cross Sensitivity: Less than 5%.

Maximum Acceleration: ±48 g.

Reading resolution must not be interpreted as absolute measurement accuracy.

5. Bearing Condition Monitoring

Bearing Condition Indicator Range: 0–3.

Supporting Measurement Parameter: Crest Factor.

Reference Diagnostic Standard: DIN ISO 13373-3.

Application: Bearing condition evaluation and long-term trend monitoring.

The bearing condition indicator does not directly represent remaining bearing lifetime.

6. IO-Link Communication

Interface Type: IO-Link.

IO-Link Version: 1.1.

Transmission Mode: COM3.

Transmission Rate: 230.4 kbit/s.

Minimum Cycle Time: 3.8 ms.

Manufacturer ID: 1475 (0x05C3).

Device ID: 2000 (0x07D0).

SDCI Standard: IEC 61131-9.

SIO Mode: Supported.

Master Port Compatibility: Class A; Class B subject to appropriate connection arrangements.

Device Description File: IODD.

Communication Functions: Process data transmission, device parameterisation, output configuration, device status information and dynamic data transfer.

7. Dynamic Data Acquisition

Transfer Mechanism: BLOB – Binary Large Object.

Acquired Signal: Raw acceleration data.

Maximum Sampling Rate: 64 kHz.

Maximum Recording Duration at 64 kHz: 5 seconds.

Lower Reference Sampling Rate: 2 kHz.

Maximum Recording Duration at 2 kHz: 160 seconds.

Application: Advanced vibration analysis using compatible external monitoring systems.

8. Output Specifications

Number of Configurable Outputs: Two.

Output 1: IO-Link interface or digital switching output.

Output 2: Analogue 4–20 mA or digital switching output.

Switching Output Type: PNP.

Maximum Switching Current: 100 mA per output.

Maximum Analogue Output Load: 500 Ω.

Analogue Output Characteristic: Proportional to the configured measuring range.

Factory Parameter Setting 001: IO-Link enabled on Output 1; Output 2 not preset.

The analogue output requires suitable configuration before operation.

9. Electrical Specifications

Supply Voltage: 18–30 VDC.

Reference Nominal Supply Voltage: 24 VDC.

Maximum Current Consumption: 320 mA.

Short-Circuit Protection: Yes.

Overload Protection: Yes.

Low Switching Level: 0 V.

High Switching Level: Supply voltage minus 2 V.

10. Mechanical Specifications

Housing Code 1: Stainless steel 1.4404 V4A, corresponding to the 316L material grade.

Mounting Thread: M8 × 8 mm.

Thread Pitch: 1.25 mm.

Width Across Flats: 24 mm.

Sensor Tightening Torque: 8 Nm.

Connector Nut Tightening Torque: 0.4 Nm.

Installation Orientation: Horizontal or vertical.

Measuring Direction: Along the mounting axis.

Electrical Connection: M12, 4-pin connector.

Duplex stainless steel 1.4462 corresponds to housing designation 2 according to the HE055 coding documentation.

11. Environmental Specifications

Reference Probe Temperature: −40 to +85°C.

Reference Ambient Temperature: −40 to +80°C.

Maximum Published Relative Humidity: 100%.

Protection Rating: IP66/IP67 when correctly connected.

Reference Enclosure Rating: Type 4X.

Outdoor Installation: Subject to applicable environmental and configuration requirements.

12. Electrical Connection

Pin 1: L+, 18–30 VDC.

Pin 2: Output 2, 4–20 mA or switching output.

Pin 3: L−, 0 V/GND.

Pin 4: Output 1, IO-Link or switching output.

The applicable operating instructions must be consulted before electrical installation.

13. Reliability Specifications

Reference Design Lifetime: 10 years.

Reference MTTF: 112.43 years.

MTTF is a statistical reliability parameter rather than a guaranteed service lifetime.

14. Standards and Certifications

DIN ISO 10816 – Evaluation of machine vibration.

ISO 20816 – Measurement and evaluation of machine vibration.

DIN ISO 13373-3 – Vibration condition monitoring and diagnostics.

DIN ISO 2954 – Requirements for vibration severity measuring instruments.

IEC 61131-9 – IO-Link/SDCI communication.

ATEX/IECEx Zone 2/22 approvals are listed for the related HE055.2.1.2.001 configuration.

The certification scope of HE055.2.1.1.001 requires individual confirmation.

SIL 2 and PL-d certification must not be assumed.

15. Key Features

Multi-parameter vibration and temperature monitoring.

Bearing condition and Crest Factor evaluation.

IO-Link COM3 communication.

Configurable analogue and digital outputs.

Dynamic raw vibration data acquisition.

Stainless steel housing construction.

Compact M8 threaded installation.

Suitable for industrial condition monitoring and predictive maintenance systems.

16. Industrial Applications

Electric motor condition monitoring.

Industrial pump vibration measurement.

Fan and blower condition monitoring.

Gearbox vibration monitoring.

Industrial compressor monitoring.

Generator bearing condition monitoring.

Automated manufacturing equipment.

Chemical processing machinery.

Water treatment equipment.

Industrial Smart Maintenance and Industry 4.0 systems.