Flowmeter MID-MDS-T-CLA-25-25-C-3A Bopp & Reuther VietNam

 

 

Magnetic inductive flow meter series MID has an integrated and detachable pre-amplifier. The coils for the magnetic field requires a 24 VAC power supply. The cable for interconnection of the meter and the converter card is approx. 5 m long (if a length of more than 5 m is required (max. 200 m), an extension cable of same type is admissible). In the event of a malfunction the pre-amplifier can be detached and replaced; no calibration of the replacement is required! The pre-amplifier is connected via plug and socket. The meter can be installed either horizontally or vertically. Vertical installation is preferred for better deaeration; and also deposits are less likely to be trapped in the meter. In the case of horizontal installation the electrodes must be in horizontal position, i.e. the pre-amplifier must be above or underneath-but not beside the meter body. If the meter is used together with a converter card UV-12 the flow direction (right to left/left to right or from below to above or vice versa) of the meter is insignificant. The UV-12 switches automatically to the given flow direction and measurement can be started immediately.