Environmental Requirements
Non-operating
Ambient Temperature: -20° to 50°C with a maximum positive/negative rate of change of 20°C/hour.
Humidity: Between 5% and 100%, non-condensing, with the maximum allowable positive/negative rate of change of 30% per hour.
Altitude: 30 m below sea level to 5000 m above sea level.
Operating
Ambient Temperature: 10°-35°C, with a maximum positive/negative rate of change of 10°C/hour.
Humidity: Between 30% and 75%, non-condensing, with the maximum allowable positive/negative rate of change of 5% per hour.
Altitude: 30 m below sea level to 2500 m above sea level
Electrical Requirements
Refer to the Specification section and to the product ID label on the rear of the LCS for the specific electrical requirements of your unit. The LCS power module is configured with a standard international IEC320/C20 inlet. To safely operate the LCS, use an SJT cord set with an IEC 320/C19 receptacle and an inlet plug that is compatible to the local power grid and the power requirements of the LCS. All Kodiak chillers should use SJT 3 conductor 12 AWG minimum power cord.